Parameter |
Description |
Range |
Standard |
UP00 |
Enable change of operation modes |
00,01 |
01 |
UP01 |
Enable change of temperature set points |
00,01 |
01 |
UP02 |
Enable change of working modes |
00,01 |
01 |
UP03 |
State after power failure |
00,01 |
00 |
UP04 |
Energy-saving mode open function |
00,01 |
00 |
UP05 |
Celsius or Fahrenheit |
00,01 |
00 |
UP06-UP18 |
Reserved parameters |
|
|
UP19 |
Lighting time 0=Normally lighting unit: seconds |
00,99 |
5 |
Parameter |
Description |
Ranger |
Standard |
1L00 |
Standby set point shift |
02—06℃ |
05 |
1L01/1L03 |
Minimum set point limit for cooling/heating |
00—10℃ |
05 |
1L02/1L04 |
Maximum set point limit for cooling/heating |
00—99℃ |
35 |
1L05 |
Temperature correction value, The actual display/10 |
00—99℃ |
00 |
1L06 |
Temperature compensation |
00—02 |
00 |
1L07-1L19 |
Reserved parameters |
|
|
IP00 |
Selection of temperature sensor 00=Internal sensor NTC,01=External sensor NTC,02=External sensor 0-10V |
00—02 |
01 |
IP01 |
Samples taken for averaging control signal |
|
10 |
IP02 |
Input overrun alarm |
00,01 |
00 |
OP00 |
Floating point output signal |
00,01 |
01 |
OP01 |
Analog output |
00,01 |
00 |
OP02 |
Minimum Limitation of output signal |
00—02 |
00 |
OP03 |
Maximum Limitation of output signal |
03—10 |
10 |
OP04 |
Time setting for floating point output |
15—95 |
90 |
OP05 |
2-pipe or 4-pipe system : 00= 2-pipe, 01= 4-pipe |
00,01 |
00 |
OP06 |
Type of digital output: 00=float-point valve;01=3-speed fan output , 02=0-10V |
00,01 |
00 |
OP07-OP15 |
Reserved parameters |
|
|
OP16 |
Dead zone between heating & cooling set point, 0.1℃ |
00-99 |
00 |
OP17 |
PID Proportional constant |
00-99 |
00 |
OP18 |
PID Integration time |
00-99 |
00 |
OP19 |
PID Derivative time |
00-99 |
00 |